Description

Template for Power Distribution unit. Performs application monitoring on PDU bank state, load state, master switch state, outlet state, etc.

Prerequisites

SNMP should be enabled in end device and device should support PowerNet-MIB OIDs and SNMP credentials should be attached against the device in portal.

How to Apply: This template is All instance selection based. It will not ask user to select any instance (s) while assigning it to a device.

Metric Parameters

Metric Parameters
ParameterDescription
Frequency
  • Frequency is the interval in which you want to probe and collect metric data from the target device/resource
  • Frequency is defined in minutes (min).
  • Warning ThresholdIf the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user.
    Critical ThresholdIf the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user.
    AlertThe alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user.

    Metrics

    pdu.bank.state

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.5.2.1.3
    ExpressionNULL
    DescriptionProvides the index to the RACK PDU Bank entry and the bank load state. Possible values are 1- Bank Load Normal, 2- Bank Load Low, 3- Bank Load Never Overlaod, 4- Bank Load Overload.
    [OID: 1.3.6.1.4.1.318.1.1.12.5.2.1.3]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Bank State
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold3[{"1":"Normal"},{"2":"Low"},{"3":"NearOverlaod"},{"4":"Overload"}]
    Warning Repeat Count11-12
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold4[{"1":"Normal"},{"2":"Low"},{"3":"NearOverlaod"},{"4":"Overload"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    pdu.loadbank.config.alarm

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.2.4.1.1.5
    ExpressionNULL
    DescriptionProvides the current bank load alarm state. Possible alarm status values are 1- No Load Alarm, 2- Under Current Alarm, 3- Near Over Current Alarm, 4- Over Current Alarm.
    [OID: 1.3.6.1.4.1.318.1.1.12.2.4.1.1.5]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Load Bank Configuration Alarm
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold3[{"1":"noLoadAlarm"},{"2":"underCurrentAlarm"},{"3":"nearOverCurrentAlarm"},{"4":"overCurrentAlarm"}]
    Warning Repeat Count11-12
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold4[{"1":"noLoadAlarm"},{"2":"underCurrentAlarm"},{"3":"nearOverCurrentAlarm"},{"4":"overCurrentAlarm"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    pdu.load.state

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.2.3.1.1.3
    ExpressionNULL
    DescriptionIndicates the phase/bank load status. phaseLoadNormal(1) indicates that the phase is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase load has dropped below the rPDULoadConfigLowLoadThreshold OID value. phaseLoadNearOverload(3) indicates that the phase load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. phaseLoadOverload(4) indicates that the phase load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value. [OID: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.3]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Load State
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold3[{"1":"Normal"},{"2":"Low"},{"3":"NearOverload"},{"4":"Overload"}]
    Warning Repeat Count11-12
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold4[{"1":"Normal"},{"2":"Low"},{"3":"NearOverload"},{"4":"Overload"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    pdu.current.load

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.2.3.1.1.2
    ExpressionrPDULoadStatusLoad/10
    DescriptionAPC PDU phase/bank current load in amps. [OIDs: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.2]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Load State
    Unitamps

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    PDU Current Load

    PDU Current Load

    pdu.outlet.state

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.4.4.2.1.3
    ExpressionNULL
    DescriptionProvides the name and the state of the outlet. Possible values are 1-Outlet On, 2- Outlet Off, 3- Outlet Reboot, 4- Outlet Unknown, 5- Outlet On With Delay, 6- Outlet Off With Delay, 7- Outlet Reboot With Delay. [OID: 1.3.6.1.4.1.318.1.1.4.4.2.1.3]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Outlet State
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorNOT_IN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold1,2[{"1":"outletOn"},{"2":"outletOff"},{"3":"outletReboot"},{"4":"outletUnknown"},{"5":"outletOnWithDelay"},{"6":"outletOffWithDelay"},{"7":"outletRebootWithDelay"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    PDU Outlet State

    PDU Outlet State

    pdu.controlled.outlets

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.3.1.3.0
    ExpressionNULL
    DescriptionThe number of controlled outlets on this Switched Rack PDU. [OID: 1.3.6.1.4.1.318.1.1.12.3.1.3.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Outlet Statistics
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    PDU Controlled Outlets

    PDU Controlled Outlets

    pdu.total.outlets

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.3.1.4.0
    ExpressionNULL
    DescriptionThe total number of outlets on this Rack PDU. [OID: 1.3.6.1.4.1.318.1.1.12.3.1.4.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Outlet Statistics
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    PDU Total Outlets

    PDU Total Outlets

    pdu.monitored.outlets

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.3.1.5.0
    ExpressionNULL
    DescriptionRepresents the PDU Outlets Monitored. [OID: 1.3.6.1.4.1.318.1.1.12.3.1.5.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Outlet Statistics
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    PDU Monitored Outlets

    PDU Monitored Outlets

    pdu.power.supply.status

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.12.4.1.3.0
    ExpressionNULL
    DescriptionIndicates the PowerSupply alarm. Possible values are 1- All Available Power Supplies OK, 2- Power Supply One Failed, 3- Power Supply Two Failed, 4- Power Supply One and Two Failed.
    [OID: 1.3.6.1.4.1.318.1.1.12.4.1.3.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Outlet Statistics
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorNOT_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold1[{"1":"allAvailablePowerSuppliesOK"},{"2":"powerSupplyOneFailed"},{"3":"powerSupplyTwoFailed"},{"4":"powerSupplyOneandTwoFailed"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    pdu.master.switch.state

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.4.2.2.0
    ExpressionNULL
    DescriptionMonitors the status of all outlets. [OID: 1.3.6.1.4.1.318.1.1.4.2.2.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC PDU Master Switch State
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorREGEX_MATCHESEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold.*Off|Unknown.*
    0..255
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    PDU Master Switch State