Description

Template for monitoring APC UPS. Monitors battery capacity, battery status, run time remaining, temperature, input line voltage, output line voltage, etc. Tested on APC Web/SNMP Management Card. System Object Id: 1.3.6.1.4.1.318.1.3.27.

Prerequisites

SNMP should be enabled in end device and device should support Powernet-MIB OIDs and SNMP credentials should be attached against the device in portal.

How to Apply: This template is All instance selection based. It will not ask user to select any instance (s) while assigning it to a device.

Metric Parameters

Metric Parameters
ParameterDescription
Frequency
  • Frequency is the interval in which you want to probe and collect metric data from the target device/resource
  • Frequency is defined in minutes (min).
  • Warning ThresholdIf the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user.
    Critical ThresholdIf the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user.
    AlertThe alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user.

    Metrics

    ups.battery.status

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.1.1.0
    ExpressionNULL
    DescriptionIndicates the status of the UPS batteries. Possible status values are 1 - Unknown, 2 - Battery Normal, 3 - Battery Low. [OID: 1.3.6.1.4.1.318.1.1.1.2.1.1 ]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold1[{"1":"unknown"},{"2":"batteryNormal"},{"3":"batteryLow"}]
    Warning Repeat Count11-12
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3[{"1":"unknown"},{"2":"batteryNormal"},{"3":"batteryLow"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Battery Status

    UPS Battery Status

    ups.no.of.batter.packs.bad

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.2.6.0
    ExpressionNULL
    DescriptionThe number of external battery packs connected to the UPS that are defective.
    [OID: 1.3.6.1.4.1.318.1.1.1.2.2.6]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold10 - 2147483647
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS No. of Bad Battery Packets

    UPS No. of Bad Battery Packets

    ups.battery.capacity

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.2.1.0
    ExpressionNULL
    DescriptionThe remaining battery capacity expressed in percent of full capacity. Alert is generated when the battery capacity is less than 99%. [OID: 1.3.6.1.4.1.318.1.1.1.2.2.1.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit%

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorLESS_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold990-100
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Battery Capacity

    UPS Battery Capacity

    ups.battery.replace.indicator

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.2.4.0
    ExpressionNULL
    DescriptionIndicates whether the UPS batteries need replacing. Possible values are 1 - No Battery Needs Replacing, 2 - Battery Needs Replacing. [OID: 1.3.6.1.4.1.318.1.1.1.2.2.4]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2[{"1":"noBatteryNeedsReplacing"},{"2":"batteryNeedsReplacing"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    ups.battery.runtime.remaining

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.2.3.0
    ExpressionupsAdvBatteryRunTimeRemaining/100
    DescriptionIndicates the UPS battery run time remaining before battery exhaustion.
    [OID: 1.3.6.1.4.1.318.1.1.1.2.2.3.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Units

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorLESS_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold18000 - 4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Battery Runtime Remaining

    UPS Battery Runtime Remaining

    ups.battery.temperature

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.2.2.0
    ExpressionNULL
    DescriptionThe current internal UPS temperature expressed in Celsius. [OID: 1.3.6.1.4.1.318.1.1.1.2.2.2.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    UnitCelsius

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold60
    0 - 4294967295
    Warning Repeat Count11-12
    Critical OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold70
    0 - 4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Battery Temperature

    UPS Battery Temperature

    ups.inputline.voltage

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.3.2.1.0
    ExpressionNULL
    DescriptionIndicates the current utility line voltage in VAC. [OID: 1.3.6.1.4.1.318.1.1.1.3.2.1.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unitv

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Input Line Voltage

    UPS Input Line Voltage

    ups.frequency.output

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.4.2.2.0
    ExpressionNULL
    DescriptionIndicates the current output frequency of the UPS system in Hz. [OID: 1.3.6.1.4.1.318.1.1.1.4.2.2]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    UnitHz

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Output Frequency

    UPS Output Frequency

    ups.load.output

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.4.2.3.0
    ExpressionNULL
    DescriptionIndicates the current UPS load expressed in percent of rated capacity.
    [OID: 1.3.6.1.4.1.318.1.1.1.4.2.3 ]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit%

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Output Load

    UPS Output Load

    ups.status.output

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.4.1.1.0
    ExpressionNULL
    DescriptionIndicates that the UPS is not supplying line voltage to any attached devices. Possible status values are 1 -Unknown, 2 - On Line, 3 - On Battery, 4 - On Smart boost, 5 - Timed Sleeping, 6 - Software Bypass, 7 - Off, 8 - Rebooting, 9 - Switched Bypass, 10-hardwareFailureBypass 11-SleepingUntilPowerReturn 12-onSmartTrim, 13-ecoMode, 14-hotStandby, 15-onBatteryTest.
    [OID: 1.3.6.1.4.1.318.1.1.1.4.1.1]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Output Status

    UPS Output Status

    ups.voltage.output

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.4.2.1.0
    ExpressionNULL
    DescriptionIndicates the output voltage of the UPS system in VAC. [OID: 1.3.6.1.4.1.318.1.1.1.4.2.1 ]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Unitv

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Voltage Output

    UPS Voltage Output

    ups.battery.time

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.318.1.1.1.2.1.2.0
    ExpressionupsBasicBatteryTimeOnBattery/100
    DescriptionThe elapsed time since the UPS has switched to battery power. Alert is generated when the time on battery is greater than 0 seconds. [OID: 1.3.6.1.4.1.318.1.1.1.2.1.2 ]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameAPC UPS Monitors
    Units

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold10 - 4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    UPS Battery Time

    UPS Battery Time